Measuring voltage transformers 38 kV:
VTS 38, VTSO 38, VTDO 38


VTS 38
Insolation voltage38,5 kV
Power frequency voltage80 kV
Impulse withstand voltage180 kV
Primary voltage3000/Ö3 - 35000/Ö3 V
Secondary voltage100/Ö3, 110/Ö3, 120/Ö3 V
Residual winding voltage100/3, 110/3, 120/3 V
Frequency50 Hz
Power30, 50, 75, 100, 150 VA
Accuracy class0.2; 0.5; 1; 3P; 6P
Thermal output500 VA
Weight34 kg



VTSO 38
Insolated voltage38,5 kV
Power frequency voltage80 kV
Impulse withstand voltage180 kV
Primary voltage3000/Ö3 - 35000/Ö3 V
Secondary voltage100/Ö3, 110/Ö3, 120/Ö3 V
Frequency50 Hz
Power30, 50, 75, 100 VA
Accuracy class0.2; 0.5; 1; 3P; 6P
Thermal output500 VA
Weight49 kg



VTDO 38
Insolated voltage38,5 kV
Powered frequency voltage80 kV
Impulse withstend voltage180 kV
Primary voltage3000 - 35000 V
Secondary voltage100, 110, 120 V
Frequency50 Hz
Power30, 50, 75, 100, 150 VA
Accuracy class0.2; 0.5; 1; 3P; 6P
Thermal output500 VA
Weight52 kg