Measuring voltage transformers 12 kV:
VTS 12, VTD 12


VTS 12
Insolation voltage12 kV
Power frequency voltage28 kV
Impulse withstand voltage75 kV
Rated primary voltage3000/Ö3 - 11000/Ö3 V
Rated secondary voltage100/Ö3, 110/Ö3, 120/Ö3 V
Residual winding voltage100/3, 110/3, 120/3 V
Frequency50 Hz
Power30, 50, 75, 100, 150 VA
Accuracy class0.2; 0.5; 1; 3P; 6P
Thermal output400 VA
Weight20 kg



VTD 12
Insolation voltage12 kV
Power frequency voltage35 kV
Impulse withstand voltage75 kV
Rated primary voltage3000 - 11000 V
Rated secondary voltage100, 110, 120 V
Frequency50 Hz
Power30, 50, 75, 100 VA
Accuracy class0.2; 0.5; 1; 3; 3P
Thermal output400 VA
Weight22 kg